This free fire extinguisher inspection checklist walks you through the monthly visual check OSHA requires for every portable fire extinguisher (29 CFR 1910.157), one unit at a time. Mark each check, see what needs action, and print this month's record or a 12-month inspection log. OSHA also requires a maintenance check each year, which the log tracks.

Extinguisher 1
  • In its designated place

    Mounted or kept where it belongs.

  • Easy to see and reach

    Nothing blocking access or the view of it.

  • Instructions readable and facing out

    Operating instructions are legible and face outward.

  • Seal and tamper indicator intact

    Nothing broken, tampered with, or missing.

  • Full

    Checked by weighing or lifting ("hefting") it.

  • No damage, corrosion, leaks or clogged nozzle

    Look over the shell, hose and nozzle.

  • Gauge in the operable range

    Pressure gauge or indicator in the green or operable position, if it has one.

  • Annual maintenance tag is less than 12 months old

    OSHA 1910.157(e)(3) requires an annual maintenance check and a record of its date.

1 extinguisher: 0 passed, 0 need action, 1 not finished.

Nothing you type leaves your browser.

Monthly fire extinguisher inspection checklist

Company: __________

Site: __________

Inspected by: __________

Date: __________

ExtinguisherIn its designated placeEasy to see and reachInstructions readable and facing outSeal and tamper indicator intactFullNo damage, corrosion, leaks or clogged nozzleGauge in the operable rangeAnnual maintenance tag is less than 12 months oldAction taken
Extinguisher 1

✓ OK · ✗ needs action · N/A. Monthly visual inspection: OSHA 29 CFR 1910.157(e)(2). Date and initial each extinguisher's tag too.

tailgatedocs.com · Free printable form. Not legal advice; adapt to your workplace.

This calculator applies the monthly inspection, annual maintenance and record rules in OSHA 29 CFR 1910.157(e), with the monthly check items fire officials list from NFPA 10. It is a planning aid, not legal advice, and it does not replace a competent person’s judgment on site.

State-plan states may set stricter requirements than the federal rule. Confirm against the standard that applies to your work before relying on a number here.

OSHA fire extinguisher inspection and maintenance schedule

TaskHow oftenWho29 CFR
Visual inspectionEvery monthYour own staff1910.157(e)(2)
Maintenance checkEvery year; record the dateTrained technician1910.157(e)(3)
Empty and maintain (stored-pressure dry chemical with a 12-year test)Every 6 yearsTrained technician1910.157(e)(4)
Hydrostatic testEvery 5 or 12 years by type (see below)Trained person with test equipment1910.157(f)
Replacement while away for serviceEvery time one is removedEmployer1910.157(e)(5)
Training on extinguisher useAt hire and at least yearlyEmployer1910.157(g)(1)-(2)

Hydrostatic test every 5 years

  • Stored pressure water and/or antifreeze
  • Wetting agent
  • Aqueous film forming foam (AFFF)
  • Loaded stream
  • Dry chemical with stainless steel shell
  • Carbon dioxide (CO2)

Hydrostatic test every 12 years

  • Dry chemical, stored pressure, with mild steel, brazed brass or aluminum shell
  • Dry chemical, cartridge or cylinder operated, with mild steel shell
  • Dry powder, cartridge or cylinder operated, with mild steel shell
  • Halon 1211
  • Halon 1301

From OSHA Table L-1 in 1910.157(f). Older soda acid and cartridge-operated water types are left out.

How to use the monthly fire extinguisher inspection log

Add each extinguisher by its number or location. Walk to it and mark each check OK, Fix, or N/A (for example, a CO2 unit has no gauge). The checks are the ones fire officials list from NFPA 10: in its place, easy to see and reach, instructions facing out, seal intact, full, no damage, and gauge in range. We added one more from OSHA: the annual maintenance tag is less than a year old.

The tool marks an extinguisher as passed only when every check is answered and none needs fixing. Any Fix answer shows what to do next. Print the monthly checklist for your file, or print the 12-month log to keep by the extinguishers and fill in by hand each month.

The monthly look is not a substitute for the yearly maintenance by a trained technician. A gauge in the green does not prove an extinguisher works; a broken seal can mean someone used part of it.

Common questions

▸How often do fire extinguishers need to be inspected?

OSHA's general industry rule requires a visual inspection every month and a maintenance check every year (29 CFR 1910.157(e)(2) and (e)(3)); on construction sites, 1926.150 requires periodic inspection under NFPA 10A. NFPA 10 says to inspect when the extinguisher is first put in service and then about every 30 days. Some stored-pressure dry chemical units also need emptying and maintenance every 6 years, and every extinguisher needs a hydrostatic test every 5 or 12 years depending on its type.

▸Do I have to keep a record of monthly inspections?

OSHA's rule names one record: the annual maintenance date, kept for one year after the last entry or the life of the shell, whichever is less. NFPA 10, the standard your local fire code may point to, also asks for the date and the initials of the person who did each monthly inspection, on a tag or label, a checklist on file, or an electronic record. A filled-in fire extinguisher inspection checklist and log covers both.

▸Who can do the monthly inspection?

Your own staff can do the monthly visual check. The annual maintenance is different: it is a thorough examination of the mechanical parts, the extinguishing agent and what pushes it out, done by a trained technician with the right tools, parts and service manual. Hydrostatic testing must be done by trained people with proper test equipment (1910.157(f)(1)).

▸What do I do if an extinguisher fails the check?

Fix simple things on the spot, such as moving it back to its place or clearing what blocks it. If it is damaged, not full, out of the gauge range, or the seal is broken, take it out of service for servicing. OSHA requires equal replacement protection while an extinguisher is away for maintenance or recharging (1910.157(e)(5)).

▸What are the fire extinguisher rules on a construction site?

OSHA 1926.150 requires at least one 2A extinguisher for each 3,000 square feet, no more than 100 feet of travel to the nearest one, at least one on each floor (next to a stairway in multistory buildings), and a 10B or larger unit within 50 feet of where more than 5 gallons of flammable or combustible liquid or 5 pounds of flammable gas is used. Extinguishers must be inspected periodically and maintained under NFPA 10A.

▸What is the difference between an inspection and maintenance?

An inspection is a quick look. OSHA defines it as a visual check that fire equipment is in place, charged, and ready for use. Maintenance is a full examination and repair of the extinguisher, done once a year or when an inspection shows a problem.

Sources

Free fire extinguisher toolbox talkOSHA self-inspection checklistLadder inspection checklistWBGT calculatorAll free safety tools